Description
The WOODWARD 9905-096 is an Automatic Generator Loading Control (AGLC) module manufactured by Woodward (Fort Collins, Colorado, USA) for use with the 2301A family of load-sharing and speed controls in multi-set and utility-parallel generating systems. It drives the soft loading and unloading of engine-generator sets once they are paralleled, ramping active power in and out at a controlled rate instead of applying or dumping load in a stepplcmasters.com+1.
Wired as the “power-for-disconnect” variant of the AGLC family and detailed in Woodward manual 82004, the 9905-096 accepts a 170–264 VAC, 50/60 Hz supply, supports fleets of 1 to 15 gensets, and provides adjustable base-load, maximum-load limit, and breaker-interlock contacts so that load transfer between parallel and island modes is bumpless and shock-freewoodward.com+2.
Application Scenarios
In a container-terminal microgrid, three 2 MW diesel gensets run in parallel during crane operations and are periodically closed onto the utility for peak-shaving. Before retrofitting, every transfer event produced an audible surge on the switchboard and frequent reverse-power trips when breakers opened under full load, forcing operators to manually feather each set down. By inserting a WOODWARD 9905-096 AGLC in front of each 2301A load-sharing system and wiring the breaker open-trip contacts through the module, the plant’s electrical supervisor achieved a 5-minute controlled unload ramp on every disconnect — frequency excursion was held inside a few tenths of a hertz, reverse-power protection stopped tripping, and the same module now brings each set back to base load automatically when the utility tie closes. This is the exact role the 9905-096 was designed to play in utility-parallel and multi-genset switchboardscnplcdcs.com+1.
Parameter
| Main Parameters | Value / Description |
|---|---|
| Product Model | WOODWARD 9905-096 |
| Manufacturer | Woodward (USA) |
| Product Category | Automatic Generator Loading Control (AGLC) module |
| Series / Companion Manual | AGLC family; Woodward manual 82004 (installation & operation) |
| Supported Gensets | 1 – 15 generator sets in parallel |
| Power Supply | 170 – 264 VAC, 50 / 60 Hz |
| Power Consumption | Approx. 5 VA |
| Control Functions | Soft load, soft unload, base-load setpoint, maximum-load limit |
| Unload Ramp Range | 5 seconds to 5 minutes (adjustable) |
| Breaker Interface | Dedicated breaker-open contact input for interlocked disconnect |
| Compatible Controls | Woodward 2301A load-sharing / speed controls (load-share line) |
| Chassis | Metal panel / chassis mount, front-access potentiometers |
| Dimensions (W × H × D) | 8.5 in × 7.5 in × 2 in (216 × 191 × 51 mm) |
| Weight | Approx. 1.02 kg (2.25 lb) |
| Operating Temperature | −40 °C to +85 °C (−40 °F to +185 °F) |
| Storage Temperature | −55 °C to +105 °C |
| Shock / Vibration | 60 Gs shock-rated, high-vibration industrial chassis |
| Safety Certifications | UL Listed, CSA Certified |
WhatsApp:+86 18005022363 WeChat: +86 18005022363