Application Scenarios
A hospital’s emergency power system relies on three paralleled diesel generators. When a utility outage occurs, the first generator starts and energizes the emergency bus, but the second and third units must be brought online without disrupting sensitive medical equipment. Closing a breaker on an unloaded generator and immediately accepting load causes a sudden frequency dip and voltage sag—a “thump” that can trip MRI machines and life-support systems. The Woodward 9905-096 solves this by initiating a controlled ramp: when the breaker auxiliary contact confirms closure, the module begins increasing the generator’s load setpoint at a preset rate until the unit reaches its share of the bus load. The transition is bumpless, and the hospital’s critical loads never see the disturbance .
Parameter
| Main Parameters | Value / Description |
|---|---|
| Product Model | Woodward 9905-096 |
| Manufacturer | Woodward Inc. |
| Product Category | Automatic Generator Loading Control (AGLC) |
| Series | AGLC Series |
| Input Voltage Option 1 | 88–132 Vac, 50/60 Hz, 2.5 VA |
| Input Voltage Option 2 | 170–264 Vac, 50/60 Hz, 5 VA |
| Ramp Rate Range | 20 to 0.33% of full load per second |
| Ramp Time | Approximately 5 seconds to 5 minutes (for 100% load change) |
| Load/Unload Ramp | Independently adjustable |
| Operating Temperature | –40 to +85 °C |
| Storage Temperature | –55 to +105 °C |
| Shock Resistance | 60 G |
| Dimensions | 8.5″ W × 7.5″ H × 2″ D (216 × 191 × 51 mm) |
| Weight | 2.25 lbs (1.02 kg) |
| Certifications | UL and CSA Listed |