Application Scenarios:In a large wastewater treatment plant, the central control system relies on a fully loaded Modicon Quantum rack with over 20 modules managing pumps, valves, and sensors. A single standard power supply cannot deliver enough current, risking voltage sags and random PLC faults. Here, two Schneider 140CPS11420 units are installed in parallel, operating in “Summ” mode. This configuration seamlessly combines their output, providing a stable 5.1V bus with ample current headroom. When one unit’s internal fan fails due to dust buildup, causing it to overheat and shut down, the second 140CPS11420 instantly assumes the full load. The PLC continues operating without a glitch, allowing maintenance to schedule a replacement during the next planned outage, directly preventing an unplanned process shutdown that could lead to environmental compliance issues.
Parameter:
| Main Parameters | Value/Description |
|---|---|
| Product Model | 140CPS11420 |
| Manufacturer | Schneider Electric (Modicon) |
| Product Category | PLC Power Supply / Backplane Logic Supply |
| Input Voltage | 115/230 V AC (Auto-sensing, 93–276 V AC, 47–63 Hz) |
| Output Voltage | +5.1 V DC (Regulated, for CPU & backplane logic) |
| Output Current | Up to 11 A (at 60°C; can be paralleled for higher capacity) |
| Power Rating | 56 W |
| Summable Operation | Yes (Parallel operation supported for redundancy or capacity) |
| Protections | Overload, Overvoltage, Short Circuit |
| Status Indication | Green PWR OK LED, Fault relay contact (Form C, 2A) |
| Operating Temperature | 0 °C to +60 °C (with derating above 40°C) |
| Housing | IP20 (For mounting inside a protected control cabinet) |
| Connection | Removable screw terminal block |
Technical Principles and Innovative Values:
- Innovation Point 1: True Summable Current Sharing Architecture: The core innovation of the 140CPS11420 is its sophisticated circuitry that allows multiple units to be connected in parallel with automatic current sharing. Unlike simple diode-ORing schemes that cause voltage drops and require external components, its internal control logic ensures all paralleled units contribute evenly to the load. This enables system designers to easily scale power capacity or implement redundancy without custom engineering, a feature that sets it apart from basic, non-summable power supplies.
- Innovation Point 2: Universal Auto-Sensing Input with Inrush Limiting: The module automatically detects and adapts to input voltages from 93V to 276V AC, covering global single-phase power standards. This eliminates manual jumpers or switches, preventing misconfiguration errors. Furthermore, it incorporates an active inrush current limiter, handling cold-start surges gracefully (up to 38A) to protect upstream circuit breakers and contactors, ensuring reliable cycling in applications like batch processing.
- Innovation Point 3: Integrated Diagnostic and Fault Reporting: Beyond the basic PWR OK LED, the 140CPS11420 provides a Form C relay contact dedicated to fault signaling. This contact can be wired directly to a PLC input or a plant alarm system. If the output voltage fails or the unit overheats, the contact changes state, providing an immediate, hard-wired alarm that is independent of the PLC’s operating status. This allows for rapid response to power supply issues before they cause a broader system failure.