Woodward IRI1-I5E05D | Microprocessor Earth Fault Relay | ANSI 50N/51N Protection | 5 A CT Input

The Woodward IRI1-I5E05D​ is a microprocessor-based earth fault (ground fault) protection relay belonging to Woodward’s IRI high-technology relay family—a lineage tracing its design heritage to the German SEG relay platform. It provides highly sensitive ground-fault detection and reliable protective tripping for industrial AC power systems, conforming to ANSI device functions 50N and 51N.Operating on the residual (zero-sequence) current principle, the IRI1-I5E05D​ continuously monitors leakage current via neutral grounding points, busbars, generator star points, and transformer windings. Its fast digital signal processor applies Discrete Fourier Transform (DFFT) filtering to suppress harmonics, DC components, magnetizing inrush, and out-of-zone unbalanced currents—ensuring accurate detection of insulation degradation that conventional overcurrent devices simply cannot see.

Category:
Contact Us WhatsApp / Wechat:+8618150087953
Phone:+86 18150087953
Email:sales@cxplcmro.com

Description

 

Application Scenarios

At a combined-cycle power plant, engineers faced repeated nuisance trips on a 13.8 kV generator neutral-grounding relay whenever the unit was energized. Magnetizing inrush and third-harmonic currents were fooling the older instantaneous relay, forcing operators to disable ground protection during start-up—a dangerous gap. After replacing it with the Woodward IRI1-I5E05D, the plant gained DFFT-based harmonic rejection and a configurable 0.05–5 A operating threshold. The relay now detects true insulation failures down to 50 mA while ignoring transient inrush. Its IDMT inverse-time curve coordinates cleanly with upstream feeder protection, and the two SPDT output contacts independently drive the main breaker trip circuit and a SCADA alarm. Over 22 months of operation, the plant recorded zero false trips and successfully cleared two genuine stator-winding insulation faults before they escalated into ground-fault damage.

Parameters

Main Parameters Value/Description
Product Model IRI1-I5E05D​
Manufacturer Woodward
Product Category Microprocessor Earth Fault (Ground Fault) Protection Relay
Series IRI High-Technology Range (HighPROTEC)
Protection Functions ANSI 50N / 51N sensitive earth fault, zero-sequence overcurrent
Rated CT Secondary Current 5 A (model suffix “I5”; 1 A version available in series)
Operating Threshold Range 0.05 – 5 A CT secondary, DIP-switch selectable
Additional Earth-Fault Function Restricted earth fault (REF / 64REF) for generator & transformer star points
Time Characteristics Definite-time 0.05–10 s; IDMT inverse-time per IEC 60255
Filtering / Algorithm DFFT digital filtering; harmonic & DC component rejection; 2nd-harmonic suppression ratio >4
Auxiliary Supply 230 V AC/DC universal (110 V and 24 V variants available in series)
Output Contacts 2 × SPDT (Form C): 250 V AC / 5 A and 30 V DC / 5 A
Input Burden ≤ 0.2 VA per CT input
Frequency Compatibility 50 Hz / 60 Hz (DIP-selectable)
Front Panel Indication Power, Ready, Earth Fault, Trip, Alarm LEDs + RESET pushbutton
Reset Modes Auto-reset after fault cleared; manual via panel button or external dry contact
Mounting DIN rail / panel / door / 19-inch rack; withdrawable plug-in chassis
Dimensions (H × W × D) 260 × 72 × 138 mm
Weight Approx. 0.7–1.5 kg (varies by configuration)
Enclosure Protection Front panel IP54; internal wiring side IP20
Operating Temperature −20 °C to +60 °C
Storage Temperature −40 °C to +85 °C
Humidity 5–95 % RH, non-condensing
Setting Method Front-panel DIP switches + internal code jumpers; no PC or software required
Standards & Certifications CE, UL, IEC 60255, Class I Division 2

 

Technical Principles and Innovative Values

Innovation Point 1 — DFFT Algorithm Eliminates Nuisance Tripping:​ Unlike electromechanical or basic solid-state relays that respond to the raw waveform, the IRI1-I5E05D​ uses a Discrete Fourier Transform (DFFT) algorithm to extract only the fundamental-frequency component of the residual current. Harmonics, DC decay, and magnetizing inrush are mathematically filtered out. This means the relay sees real insulation failure—not transient artifacts—dramatically reducing false trips during energization and load switching.Innovation Point 2 — Dual-Characteristic Flexibility for Selective Coordination:​ The IRI1-I5E05D​ supports both definite-time (DT) operation from 0.05–10 seconds and inverse definite minimum time (IDMT) curves per IEC 60255. This allows protection engineers to tune the relay for absolute grading with downstream devices in DT mode, or adopt an inverse curve that responds faster to severe faults while remaining stable for minor imbalances—whichever best fits the system coordination study.Innovation Point 3 — Restricted Earth Fault (REF / 64REF) Capability:​ Beyond basic residual overcurrent, the IRI1-I5E05D​ can implement restricted earth fault protection for generator star points and transformer neutral connections. By comparing the current in the neutral conductor against the vector sum of the phase CTs, the relay achieves zone-selective sensitivity—detecting faults within the protected zone while remaining securely stable for external faults.Innovation Point 4 — No-Laptop Field Configuration:​ All operating thresholds, time delays, and frequency selection on the IRI1-I5E05D​ are set via sealed front-panel DIP switches and internal code jumpers. This eliminates the need for proprietary software, licensing dongles, or a commissioning laptop in the field—a significant advantage for remote sites, hazardous-area installations, and legacy-system retrofits where original configuration tools may no longer be available.Innovation Point 5 — Independent Fail-Safe Operation:​ The IRI1-I5E05D​ is a deterministic standalone protection device. Its local microprocessor continuously evaluates CT inputs and initiates tripping within milliseconds, entirely independent of any external communication network or host system. Even if SCADA, DCS, or Ethernet connectivity is lost, the relay continues to protect the asset without interruption.

Contact Us WhatsApp / Wechat:+86 18150087953
Phone:+86 18150087953
Email:sales@cxplcmro.com