Description
Technical Specifications
表格
| Parameter Name | Parameter Value |
|---|---|
| Product Model | IRI1-I5E05D |
| Manufacturer | Woodward |
| Product Type | Microprocessor Sensitive Earth Fault Protection Relay |
| Protection Functions | ANSI 50N / 51N Sensitive Earth Fault, Zero-sequence Overcurrent |
| Rated CT Secondary Current | 5 A |
| Operating Threshold Range | 0.05 – 5 A (CT secondary side, DIP-switch selectable) |
| Time Characteristics | Definite-time 0.05–10 s; IDMT inverse-time per IEC 60255 |
| Filtering Algorithm | DFFT digital filtering, harmonic & DC component rejection |
| Auxiliary Supply | 230 V AC/DC universal (180–250 V wide range) |
| Output Contacts | 2× SPDT (Form C), 250 V AC / 5 A, 30 V DC / 5 A |
| Operating Frequency | 50/60 Hz adaptive |
| Working Temperature | −20 °C ~ +60 °C |
| Physical Dimensions | 72 × 138 × 260 mm |
| Weight | Approximately 1.5 kg |
| Installation Method | DIN rail or panel flush mounting |
| Front Panel Protection | IP54 (sealable transparent flap) |
| Compliance Certifications | CE, UL, IEC 60255 |
Main Features and Advantages
Ultra-high detection sensitivity: The Woodward IRI1-I5E05D offers an extremely wide, finely graded current setting range from 0.05% to 36% of the rated 5A CT secondary current, enabling it to capture very low-level leakage currents that conventional earth fault relays cannot detect, providing early protection for high-impedance ground faults.
Strong anti-interference performance: Built-in DFFT digital filtering and low-pass filter architecture effectively eliminates harmonic distortion, transient surges, and DC component interference, ensuring the Woodward IRI1-I5E05D will not generate nuisance tripping caused by external electrical noise, even in industrial sites with heavy variable frequency load and complex electromagnetic environments.
Flexible configuration and easy operation: All protection parameters of the Woodward IRI1-I5E05D are adjusted via DIP switches on the front panel, no complex software programming is required, and users can quickly complete on-site setting and commissioning. It supports two reset modes: self-holding and automatic reset for LED indicators and trip relays, which can be adapted to different system operation management habits.
Wide environmental adaptability: The Woodward IRI1-I5E05D adopts an industrial-grade rugged design, with a wide operating temperature range from -20°C to +60°C, and supports universal AC/DC 230V auxiliary power supply, which can operate stably in harsh industrial scenarios such as outdoor switch rooms, high-humidity workshops, and high-altitude areas. The compact housing supports both DIN rail installation and panel flush mounting, which can be seamlessly integrated into various standard switchgear cabinets without modifying the original panel structure.
Application Field
The Woodward IRI1-I5E05D is widely used in industrial power systems that require high-sensitivity ground fault protection, and its core application scenarios cover multiple key industrial fields. In the power generation industry, it is installed at the neutral point of generators and the star point of transformers, providing independent restricted earth fault protection for large-scale generating units, effectively preventing winding insulation breakdown and equipment burnout accidents caused by hidden ground faults.
In the field of industrial manufacturing and petrochemicals, the Woodward IRI1-I5E05D is deployed in medium-voltage and low-voltage distribution networks, high-voltage motor loops, and complete sets of switchgear, which can quickly identify insulation aging faults of cables and motors, avoid electric shock risks to on-site personnel, and prevent unplanned production shutdowns caused by ground fault expansion. It is also very suitable for isolated neutral or resistance-earthed industrial power grids, and can accurately detect small leakage currents without misoperation during external fault cross-over.
In the municipal and utility industries, the Woodward IRI1-I5E05D is used in urban power distribution stations, water treatment plant power distribution systems, and data center power supply loops, providing reliable ground fault monitoring and protection for critical power loads, ensuring the continuous and stable operation of key infrastructure. Its two independent SPDT output contacts can be respectively connected to the alarm loop and the trip loop, realizing the layered protection logic of “early warning for minor faults and immediate tripping for serious faults”, which greatly improves the safety and operation reliability of the entire power system.
WhatsApp:+86 18005022363 WeChat: +86 18005022363
Email: