Description
Technical Specifications
| Parameter Name | Parameter Value |
|---|---|
| Product Model | 9907-135 |
| Manufacturer | Woodward |
| Product Type | Actuator / Valve Driver Module |
| Compatible Platform | Woodward 505 / 505E Digital Turbine Governor |
| Input Signal | 4–20 mA / ±10 VDC governor command |
| Output Type | Proportional current drive for torque motor / solenoid |
| Output Current Range | 4–20 mA or 20–160 mA (configurable) |
| Output Compliance | Sufficient to drive EHA / proportional valve coils |
| Control Method | Closed-loop current regulation |
| Protection Features | Short-circuit, over-current, feedback-loss, reverse-polarity |
| Diagnostics | Output current monitoring, coil continuity, fault status |
| Operating Temperature | -40 °C to +85 °C |
| Power Supply | 24 VDC system supply |
| Mounting | Control cabinet / 505 chassis |
| Certifications | Designed to applicable industrial EMI/RFI standards |
Main Features and Advantages
The primary value of the Woodward 9907-135 lies in its role as a precision power interface. The governor can calculate the ideal valve position to within a fraction of a percent, but without an accurate, stable driver stage that demand will never reach the actuator cleanly. The Woodward 9907-135 provides closed-loop current control, meaning the actual drive current is sampled and corrected continuously—even as actuator coil resistance changes with oil temperature or ambient conditions, valve position does not drift.Closed-loop current regulation for accurate positioning:Unlike a simple voltage amplifier, the Woodward 9907-135 regulates the current delivered to the torque motor or solenoid. This is the physically meaningful quantity for actuator force: a given current produces a given magnetic force, regardless of coil heating or supply variation. The result is repeatable, linear valve positioning—critical for stable speed control, especially during turbine start-up ramps, load changes, and fuel-transfer windows on dual-fuel engines.Built-in protection and diagnostics:The Woodward 9907-135 monitors output current, coil continuity, and internal fault conditions. Open coils, shorted outputs, and loss of command signal are detected and can be reported to the 505E governor, which may then raise an alarm or initiate a controlled trip depending on how the actuator-fault logic is configured. This protects both the driver electronics and the expensive actuator hardware downstream, and it gives maintenance staff a clear first indicator when valve performance degrades.Rugged industrial design:Designed for turbine enclosures rather than benign office environments, the Woodward 9907-135 tolerates wide temperature swings, vibration, humidity, and electrical noise. Its signal isolation between input and output stages helps prevent ground loops and transducer-induced disturbances from propagating into the actuator drive. These characteristics support the long service intervals and high availability expected of governor equipment in continuous-process industries.
Application Field
The Woodward 9907-135 is used wherever a Woodward 505 or 505E governor needs to drive an electro-hydraulic final element. In steam turbine generator sets—found in captive power plants, combined heat and power (CHP), and waste-to-energy facilities—the module drives the steam admission valve, translating the governor’s speed/load control into precise valve positioning for frequency regulation and load sharing between parallel machines.In gas turbine packages, the Woodward 9907-135 drives fuel-metering actuators, supporting start-up ramp control, acceleration limiting, and load management. For dual-fuel applications, separate driver channels may control gas and liquid-fuel valves under a single governor strategy; the driver’s stable current regulation ensures smooth, bumpless fuel transfer without combustion instability. In mechanical-drive turbines used in refineries and petrochemical plants, the module controls steam valves that regulate turbine speed to drive compressors, fans, and process pumps.The module also supports turbine control retrofit projects: when upgrading legacy mechanical or electro-hydraulic governors to a modern 505E digital platform, the Woodward 9907-135 allows reuse of existing actuator hardware while providing the modern, closed-loop drive stage the new governor requires. This shortens outage time and preserves the investment in proven field equipment.
WhatsApp:+86 18005022363 WeChat: +86 18005022363