Yokogawa ANB11D-225 Rack-Mount Optical ESB Bus Node Unit – 5km Fiber I/O Aggregation

The ANB11D-225​ is a Yokogawa optical ESB (Extended Serial Backbone) bus node unit belonging to the ANB11D series of dual-redundant node units with built-in optical repeaters, designed for N-IO/FIO remote I/O cabinets in CENTUM VP and CENTUM CS 3000 distributed control systems. It functions as the physical and electrical aggregation hub that collects analog and contact I/O signals from up to eight field I/O modules, converts the data stream for transmission over fiber optic cable, and supplies regulated power to all mounted I/O modules—extending the reach of a Yokogawa Field Control Unit (FCU) from the customary copper-bus limit of a few meters out to 5 km (or 50 km with an upgraded repeater slave), all while preserving fully dual-redundant power and bus paths.

Category:
Contact Us WhatsApp / Wechat:+8618150087953
Phone:+86 18150087953
Email:sales@cxplcmro.com

Description

横川ANB11D-225光学ESB总线节点单元1

 

Application Scenarios

A Middle Eastern ethylene cracker faced chronic control instability because its FCU resided in a central control building while the field I/O had to be distributed across a compressor station more than three kilometers away. Running copper ESB cable was never an option—the site’s own medium-voltage switchgear and dozens of variable-frequency drives generated ground-potential differences and electromagnetic noise that repeatedly corrupted backplane traffic. By installing the ANB11D-225​ in a remote 19-inch rack at the compressor skid and pairing it with an ANT401-series master repeater at the FCU, the plant converted the entire inter-cabinet link to single-mode fiber. The optical path eliminated galvanic coupling between buildings, shrugged off the VFD-generated EMI that had plagued the old copper runs, and kept every analog input and contact output online with no re-engineering of the existing FIO modules. For the operations team, the ANB11D-225​ turned what had been a noise-driven maintenance headache into a transparent, self-healing link—exactly the kind of unglamorous infrastructure that keeps a continuous-process plant from tripping on a single cable fault.

Parameter

Main Parameters Value/Description
Product Model ANB11D-225 (full suffix ANB11D-225/BU2A or /BU2B)
Manufacturer Yokogawa Electric Corporation (Japan)
Product Category Optical ESB Bus Node Unit for N-IO/FIO, dual-redundant bus with optical repeater
Compatible Systems CENTUM VP, CENTUM CS 3000 (via AFV30□ / AFV40□ FCU)
Power Supply 220–240 V AC, 50/60 Hz (suffix “2”); optional 100–120 V AC or 24 V DC
Redundancy Dual-redundant power supply + dual-redundant ESB bus (automatic failover)
Optical Repeater Distance 5 km with ANT401 slave module (50 km upgradeable with ANT411/ANT512)
Transmission Medium Single-mode quartz optical fiber
Transmission Speed 192 Mbps (optical ESB bus)
I/O Slot Capacity 8 slots; 2 fixed for ESB interface modules, 6 for I/O modules
Power Consumption 230 VA / 120 W (220–240 V AC); 200 VA / 120 W (100–120 V AC); 5.5 A (24 V DC)
Physical Dimensions 482.6 (W) × 132.5 (H) × 310 (D) mm
Weight Approx. 10 kg including 8 I/O modules
Mounting 19-inch EIA rack mount, 4 × M5 screws
Operating Temperature 0 to 50 °C basic type; –20 to 70 °C with G3 option
Compliance CE, CSA, C-Tick, KC, FM Non-Incendive, Type n; explosion-protected variants available
Required Accessory ESB Bus Coupler Module EC401 or EC402 in FCU slots IO7/IO8

 

Technical Principles and Innovative Values

  • Innovation Point 1 – Optical isolation that kills ground loops at the source.​ Where copper ESB is constrained to roughly 10 m and couples every potential difference between cabinets, the ANB11D-225​ launches the I/O data onto single-mode fiber. Dielectric isolation severs the ground reference between buildings, so the voltage gradients that once rode the shield now have no path through the control system.
  • Innovation Point 2 – Native dual-redundancy without external multiplexing.​ Both the power supply and the ESB bus are internally paired. If one feeder sags or one fiber is cut, the surviving path assumes the load with no I/O interruption and no operator intervention—no relay logic, no programmable workaround, no single point of failure in the node itself.
  • Innovation Point 3 – Deterministic 192 Mbps backplane under full load.​ Channel-to-channel isolation in the mounted FIO modules suppresses ground-loop currents, while integrated cold-junction compensation on compatible analog input modules preserves thermocouple accuracy. Scan time stays bounded regardless of how many slots are populated.
  • Innovation Point 4 – Scalable distance through a swappable repeater ecosystem.​ The “2” suffix specifies the 5 km repeater class (ANT401 master / ANT502 slave). Moving to 50 km is a matter of selecting the “4” suffix with ANT411/A2EN501 and ANT512—the node housing, cabling philosophy, and I/O complement remain unchanged.
  • Innovation Point 5 – Modular composition rather than fixed-function hardware.​ Power supply modules, the optical repeater module, bus interface modules, and FIO modules all seat in the same rack frame, letting engineering scale slot count, power, and environment-proofing (G3, –20 to 70 °C, explosion protection) independently.
Contact Us WhatsApp / Wechat:+86 18150087953
Phone:+86 18150087953