Application Scenarios
At a Southeast Asian refinery undergoing a phased SIS modernization, the integrator was asked to replace a legacy trip system with a TÜV-certified SIL3 logic solver without disturbing the existing CENTUM VP operator stations, the field wiring, or the I/O termination architecture that had been commissioned years earlier. Deploying the Yokogawa SSC10D-S2111 as the SIS controller solved the engineering conflict directly: because the SSC10D-S2111 rides on the same Vnet/IP backbone and uses the same engineering environment as the CENTUM VP DCS, process control and safety logic could be engineered, trended, and operated under one unified human-machine interface — eliminating the multi-vendor alarm storm that had historically plagued the control room during upset conditions. The SSC10D-S2111 is the standard logic solver in exactly this class of deployment: ESD (Emergency Shutdown), Burner Management Systems, Fire & Gas voting logic, HIPPS high-integrity pressure protection, and turbine/compressor safeguarding across refining, petrochemical, offshore, and power-generation assets where Yokogawa DCS infrastructure already exists and SIL3 integrity is non-negotiable.excellentplc.com+1
Parameter
| Main Parameters | Value / Description |
|---|---|
| Product Model | Yokogawa SSC10D-S2111 |
| Manufacturer | Yokogawa Electric Corporation (Japan) |
| Product Category | Duplexed Safety Control Unit (SIS Logic Solver) |
| System Platform | Yokogawa ProSafe-RS SIS / CENTUM VP / CENTUM CS3000 |
| Suffix Code Decoding | SSC10D Duplexed / -S Standard (-20 to 50 °C, ISA G3) / 2 Dual-redundant PSU / 1 Fixed / 1 100–120 VAC / 1 CFS1100 License |
| Processor | MIPS R5000, 32-bit RISC, dual-CPU 1oo2D architecture |
| Main Memory | 32 MB (battery-backed, up to 3 years @ ≤30 °C) |
| Safety Integrity Level | SIL3 per IEC 61508 / IEC 61511, TÜV certified |
| Scan Cycle | Deterministic, configurable 10–100 ms (typical ≤50 ms) |
| Redundancy Switchover | ≤1 ms, bumpless, automatic on CPU fault |
| Communication | Dual-redundant Vnet/IP; Dual-redundant ESB bus |
| Node Expansion | Up to 9 Safety Node Units (SNB10D) per SSC10D-S2111 |
| Local I/O Modules | Up to 8 per unit; up to 78 per SCS |
| Power Supply | 100–120 VAC, 50/60 Hz (dual redundant), ≈200 VA |
| Dimensions (W × H × D) | 482.6 × 88.1 × 266 mm (19-inch, 2U) |
| Weight | ≈8.5 kg (SSC10D-S) |
| Mounting | 19″ rack mount, 8 × M5 screws, insulation bushings supplied |
| Optional Codes | /GPS (IRIG-B GPS time sync, S9161FA), /ATDOC (ATEX manual) |
| Software Requirement | CFS1100 Safety Control Functions Package (license included in -S2111) |
| Programming Tool | SCS Logic Designer (IEC 61131-3 function block) |
| Standards | CE, ATEX (with /ATDOC), IECEx, CSA, UL, RoHS |