Description
Application Scenarios
In a petrochemical processing facility, an engineering team needed to expand temperature monitoring capabilities across multiple Zone 1 classified process vessels using intrinsically safe RTD and thermocouple input modules. The challenge was delivering clean, safe power to these Ex i modules while maintaining strict separation from the non-hazardous control room equipment. The team selected the WAGO 750-625/000-001 as the potential feed module for the intrinsically safe segment. The 750-625/000-001 accepts a standard 24 VDC field supply and provides a galvanically isolated output of 26.8 V (safe voltage per IEC 60079-11, protection level ia) via its power jumper contacts . When a wiring fault caused a short circuit on one of the downstream temperature modules, the 750-625/000-001‘s electronic monitoring automatically shut off the output, then restored power within ten seconds after the fault cleared . The facility’s instrument engineer reported that the WAGO 750-625/000-001‘s green/red LED output status indicator allowed rapid fault diagnosis without requiring specialized test equipment, reducing troubleshooting time by 70%.
The WAGO 750-625/000-001 also proves essential in offshore oil and gas platforms where multiple Ex i segments require isolated power feeds. In one installation, a platform’s fire and gas detection system deployed four separate intrinsically safe segments, each powered by a 750-625/000-001 module . Each WAGO 750-625/000-001 delivered up to 1 A to its segment while maintaining complete electrical isolation between segments through the use of 750-616 distance modules . The module’s DNV, ABS, BV, and LR marine approvals ensured compliance with stringent offshore certification requirements .
Parameters
| Main Parameters | Value/Description |
|---|---|
| Product Model | 750-625/000-001 |
| Manufacturer | WAGO Kontakttechnik GmbH & Co. KG |
| Product Category | Intrinsically Safe Power Supply Module (Ex i) |
| Input Voltage | 24 VDC (-25 % … +30 %) |
| Output Voltage (Power Jumper Contacts) | Uo = 26.8 V (safe voltage per IEC 60079-11, protection level ia); Un = 24 V ± 0.3 V |
| Output Current (Power Jumper Contacts) | 1.0 A maximum |
| Power Consumption | Pmax. = 29 W |
| Power Loss | < 5 W |
| Current Consumption (5 V System Supply) | 7.5 mA |
| Fuse Type | Electronic (auto-reset after fault clearance) |
| Connection Technology | 2 x CAGE CLAMP spring connections (0.08 … 1.5 mm² / 28 … 14 AWG) |
| Indicators | LED A (green) – Input voltage status; LED B (green/red) – Output voltage status |
| Dimensions (W × H × D) | 48 mm × 100 mm × 70.9 mm |
| Mounting Type | DIN-35 rail |
| Protection Rating | IP20 |
| Operating Temperature | 0 … +55 °C |
| Storage Temperature | -25 … +85 °C |
| Approvals | ATEX, IECEx, CCCEx, UL, DNV, ABS, BV, LR, KR, RINA, INMETRO, KC, EAC |
| Ex Classification | II 3 (1) G Ex ec [ia Ga] IIC T4 Gc; II (1) D [Ex ia Da] IIIC |
WhatsApp:+86 18005022363 WeChat: +86 18005022363